Peach Bottom Atomic Power Station: Major Loss of Emergency Preparedness Capabilities
Peach Bottom - LOSS OF TECHNICAL SUPPORT CENTER VENTILATION SYSTEM
U.S. Nuclear Regulatory Commission
Operations Center
Operations Center
Event Reports For
8/11/2020 - 8/12/2020
8/11/2020 - 8/12/2020
** EVENT NUMBERS **
Power Reactor
|
Event Number: 54829
|
Facility: Peach Bottom
Region: 1 State: PA Unit: [2] [3] [] RX Type: [2] GE-4,[3] GE-4 NRC Notified By: John Whelan HQ OPS Officer: Brian P. Smith |
Notification Date: 08/11/2020
Notification Time: 20:22 [ET] Event Date: 08/11/2020 Event Time: 13:34 [EDT] Last Update Date: 08/11/2020 |
Emergency Class: Non Emergency
10 CFR Section: 50.72(b)(3)(xiii) - Loss Comm/Asmt/Response |
Person (Organization):
MEL GRAY (R1DO) |
Unit
|
SCRAM Code
|
RX Crit
|
Initial PWR
|
Initial RX Mode
|
Current PWR
|
Current RX Mode
|
|||||||
2
|
N
|
Y
|
97
|
Power Operation
|
97
|
Power Operation
|
|||||||
3
|
N
|
Y
|
100
|
Power Operation
|
100
|
Power Operation
|
Event Text
LOSS OF TECHNICAL SUPPORT CENTER VENTILATION SYSTEM
"At 1334 EDT on Tuesday August 11th, the Peach Bottom Atomic Power Station (PBAPS) Technical Support Center (TSC) Ventilation System lost power due to a trip of the Station Blackout (SBO) electric power supply breaker. The trip was due to a fault at the Conowingo Dam and Conowingo was not able to realign electric power to the SBO within an hour. Power restoration is complete and TSC Ventilation was restored at 1725 EDT. "This report is being submitted pursuant to 10CFR 50.72(b)(3)(xiii) as a Major Loss of Emergency Preparedness Capabilities due to a reduction in the effectiveness of the Onsite Technical Support Center (TSC). "The NRC Resident Inspector has been notified." |
- Log in to post comments